3 ways isolated universal signal converterDAT4235 3 ways isolated universal signal converter

FEATURES

 

Configurable input for RTD, TC, mV, V, mA, Resistance and Potentiometer

Galvanic isolation at 2000 Vac on the 3 ways

Configurable output in current or voltage

Configurable by Personal Computer

High accuracy

On-field reconfigurable

EMC compliant – CE mark

Suitable for DIN rail mounting in compliance with EN-50022 and EN50035

 

 

 

 

 

 

Click here to request Information.

3 ways isolated universal signal converter

3 ways isolated universal signal converter

 

 

 

 

 

 

 

 

 

 

 

 

3 way isolated universal input Converter DAT4235 with PC programmability.

GENERAL DESCRIPTION

The isolated universal Converter DAT4235 is a Din Rail mount signal transmitter with PC programmability. The input can be thermocouples, RTD, mA, V, mV, resistance and potentiometer. The DAT4235 will linearize the input and provide a 4-20mA or voltage output signal.

The DAT4235 is accurate to 0.1% full scale and has less than 0.01%/'f thermal drift.

The DAT4235 is programmable by PC based software which has been developed by DATEXEL to be user friendly.

For resistance and RTD's sensors it is possible to program the cable compensation for 3 or 4 wires.

It is possible to set the minimum and maximum values of the input and output ranges in any point of the scale, keeping the minimum span shown in the table below. Also high burn out alarm or low burn out alarm is selectable.

The DAT4235 is isolated between the power supply and the input/output to 2000V, eliminates the effects of any ground loops and allows the use of the transmitter in heavy environmental conditions found in industrial applications.The DAT4235 is in compliance with the standard 89/336/CEE on the Electromagnetic Compatibility.

Suitable for the following thermocouples.

K Type Thermocouples

J Type Thermocouples

S Type Thermocouples

R Type Thermocouples

B Type Thermocouples

E Type Thermocouples

T Type Thermocouples

N Type Thermocouples

Suitable for the following RTD.

Pt100

Pt1000

Ni100

Ni1000

The DAT4235 is housed in a plastic enclosure of 12.5 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.

The DAT4235 is able to measure and linearize the standard thermocouples with internal cold junction compensation.

USER INSTRUCTIONS

The converter DAT4235 must be powered by a direct voltage between 18 to 30 V applied to the terminals Q(+Vdc) and R (GND1) as shown in the section "Power supply connections".

The output signal, in voltage or current, is provided to the terminals N(OUT) and M (GND2), as shown in the section "Output connections".

The input connections must be made as shown in the section "Input connections".

To configure, calibrate and install the converter, refer to sections " DAT4235: configuration and calibration" and “Installation Instructions”.

TECHNICAL SPECIFICATIONS

3way-isolated

isolated-signal-convertor

INSTALLATION INSTRUCTIONS

The device DAT4235 is suitable for DIN rail mounting. It is necessary to install the device in a place without vibrations; avoid to routing conductors near power signal cables .

CONFIGURATION AND CALIBRATION

Warning: during these operations the device must always be powered.

CONFIGURATION

1) Power-on the DAT4235 by a direct voltage between 18 - 30 V.

2) Open the plastic label protection on front side of DAT4235.

3) Connect the interface PRODAT to the Personal Computer and to device (connector PGRM - see section “ DAT4135/SEL: PROGRAMMING” ).

4) Run the software PROSOFT.

5) Set the parameters of configuration .

6) Program the device.

CALIBRATION CONTROL

With software PROSOFT running:

1) Connect on the input a calibrator setted with minimum and maximum values referred to the electric signal or to the temperature sensor to measure.

2) Set the calibrator at the minimum value.

3) Verify that the DAT4235 provides on output the minimum setted value.

4) Set the calibrator at the maximum value.

5) Verify that the DAT4235 provides on output the maximum setted value.6) In case of regulation of value obtained in the step 3 and 5, use the ZERO and SPAN regulators of software PROSOFT. The variation introduced from these regulators must be calculated as percentage of the input range .

7) Program the device with the new parameters .

PROGRAMMING

isolated-signal-convertor

CONNECTIONS

thermocouple-converotr-

DIMENSIONS (mm)

din-rail-isolator

ISOLATION STRUCTURE

rtd-isolator

HOW TO ORDER

k-type-thermocouple-isolator