Regulated Power supplyDat410

FEATURES

AC line input: 24, 120 or 230 Vca @ 50-60 Hz

One galvanic isolated output

Power supply unit for transmitters

EMC compliant

CE mark

In compliance with the safety standard

Suitable for DIN rail mounting in compliance with EN 50022 and EN-50035

 

 

 

 

 

 

Signal Conditioning by DATEXEL

 

Click here to request Information.

 

 

 

 

 

 

 

 

 

 

 

 

DAT411SR Regulated Power supply.

GENERAL DESCRIPTION

The power supply unit DAT411SR is designed to provide a isolated regulated output to power the DATEXEL devices like transmitters and converters.

The device can accept three input voltage values:24, 120 or 230 Vac.

The DAT411SR is in compliance with the standard 89/336/EEC on the Electromagnetic Compatibility.

It is housed in a plastic enclosure of 28 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.

 

USER INSTRUCTIONS

The DAT411SR must be connected as follows:

The input connections must be made as shown in the section "Input connections".

The input voltage ( AC line ) must be applied between the terminals G ( IN AC) and H ( IN AC ).

The output connections must be made as shown in the sections “Output connections”

The output signal is provided between the terminals F (+Vout) and E (GND),

To install the transmitter refer to section “Installation Instructions”.

TECHNICAL SPECIFICATIONS

Input  
Input voltage

24 Vac ± 10 % @ 50-60 Hz.

120 Vac ± 10 % @ 50-60 Hz.

230 Vac ± 10 % @ 50-60 Hz.

Outputs  
Output 20 Vdc @ 55 mA regulated.
Load resistance (Rload) see section “Load characteristic”
Environmental data  
Safety EN 61010-1 Electromagnetic Compatibility (EMC) ( for industrial environments)
Immunity: EN 61000-6-2; Emission : EN 61000-6-4.
Operating Temperature -20 ÷ 70 °C
Storage Temperature -40 ÷ 85 °C
Humidity (not condensed) 0 ÷ 90%
Weight about 130 g

INSTALLATION INSTRUCTIONS

The device DAT411SR is suitable for DIN rail mounting.
It is necessary to install the device in a place without vibrations; avoid to routing conductors near power signal cables .

Dimensions (mm)

DAT411 Dimensions

 

Load Characteristic

DAT411SR Load Characteristic

 

Connections

DAT411SR Connections

 

Isolation Structure

Isolation Structure DAT411