RTD Temperature transmitterDAT1065 Isolated Temperature Transmitter Head mount Datexel Dip Switch Programmable Thermocouple RTD

FEATURES

Configurable input for RTD, mV, Resistance and Potentiometer

4 ÷ 20 mA configurable output on current loop

Configurable by Personal Computer

High accuracy

On-field reconfigurable

EMC compliant

CE mark

Suitable for DIN B in-head mounting

Option for DIN rail mounting in compliance with EN 50022 (DIN RAIL Option)

 

 

 

 

 

Signal Conditioning by DATEXEL

 

Call Toll Free for more Information

1 877 4to 20mA

1 877 486 2062

24/7 Support

1 225 200 7419

Click here to request Information.

DAT1065 Isolated Temperature Transmitter Head mount Datexel Dip Switch Programmable Thermocouple RTD

DAT1065 Isolated Temperature Transmitter Head mount Datexel Dip Switch Programmable Thermocouple RTD

 

 

 

 

 

 

 

 

 

 

 

 

RTD Temperature Transmitter DAT1070 with PC programmability.

GENERAL DESCRIPTION

The low profile temperature Transmitter DAT1070 is an RTD hockey puck (head mount) temperature Transmitter with PC programmability. The input can be Pt100, Pt1000, Ni100, Ni1000 or mV and potentiometer. The DAT1070 will linearize the temperature input and provide a 4-20mA output signal.

The DAT1070 is accurate to 0.1% full scale and has less than 0.01%/'f thermal drift.

The DAT1070 is programmable by PC based software which has been developed by DATEXEL to be user friendly.

For resistance and RTD's sensors it is possible to program the cable compensation for 3 or 4 wires.

It is possible to set the minimum and maximum values of the input and output ranges in any point of the scale, keeping the minimum span shown in the table below. Also high burn out alarm or low burn out alarm is selectable.

The DAT1070 is in compliance with the standard 89/336/CEE on the Electromagnetic Compatibility.

The DAT1070 is housed in a self-extinguish plastic enclosure suitable for DIN B in-head mounting.

There is a mounting kit available to mount the DAT1070 on DIN rail.

USER INSTRUCTIONS

The RTD Temperature transmitter DAT1070 must be powered by a direct voltage between 10 to 32 V and applied to the terminals +V and -V.

The 4÷20 mA output signal is measurable in the power loop as shown in the section “Output/Power supply connections”; Rload is the input impedance of instruments on the current loop; to obtain a correct measure, the value of Rload will be calculated as function of the power supply value ( see section “Technical specification – Load characteristic”).

The input connections must be made as shown in the section "Input connections".

To configure, calibrate and install the transmitter refer to sections " DAT1070: configuration and calibration" and “Installation Instructions”.

TECHNICAL SPECIFICATIONS

Input type Min Max Min. span
RTD(*) 2,3,4 wires      
Pt100 -200°C 850°C 50°C
Pt1000 -200°C 200°C 50°C
Ni100 -60°C 180°C 50°C
Ni1000 -60°C 150°C 50°C
Voltage      
mV -100mV +700mV 2 mV
Potentiometer      
(Nominal value) 0 Ohm 200 Ohm 10%
  200 Ohm 500 OhM 10%
  0.5 KOhm 2 KOhm 10%
RES. 2,3,4 wires      
Low 0 Ohm 300 Ohm 10 Ohm
High 0 Ohm 2000 Ohm 200 Ohm
Output type Min Max Min. span
Direct current 4 mA 20 mA 4 mA
Reverse current 20 mA 4 mA 4 mA
Input calibration (1)  
RTD > of ±0.1% f.s. or ±0.2°C
Low res. > of ±0.1% f.s. or ±0.15 Ohm
High res. > of ±0.2% f.s. or ±1 Ohm
mV > of ±0.1% f.s.or ±18 uV
Output calibration  
Current ± 7 uA
Input impedance  
mV >= 10 MOhm
Linearity (1)  
RTD ± 0.1 % f.s.
Line resistance influence  
mV <=0,8 uV/Ohm
RTD 3 wires 0.05%/Ohm (50 Ohm balanced max.)
RTD excitation current  
Typical 0,350 mA
Thermal drift (1)  
Full scale ± 0.01% / °C
Burn-out values  
Max. value about 22.5 mA
Min. value about 3.6 mA
(1) referred to input Span (difference between max. and min. values)  
Performances  
Response time ( 10÷ 90%) about 400 ms
Power supply voltage (**) 10÷32 Vdc
Reverse polarity protection 60 Vdc max
Electromagnetic Compatibility (EMC)
( for industrial environments ) Immunity:
EN 61000-6-2; Emission : EN 61000-6-4.
Operating Temperature -20 ÷ 70 °C
Storage Temperature -40 ÷ 85 °C
Humidity (not condensed) 0 ÷ 90%
Mounting DIN B head or bigger
Weight about 50 g.
Dimensions = 43 mm ; H = 17 mm
(*) For temperature sensors it is possible to set the input range also in F degrees; to made the conversion use the formula: °F = (°C*9/5)+32)  

INSTALLATION INSTRUCTIONS

The device DAT1070 is suitable for direct DIN B in-head mounting. The transmitter must be fixed inside the probe by the proper kit.

By apposite stirrup, provided on request, it is possible to mount the device on DIN rail in compliance with EN-50022.

It is necessary to install the device in a place without vibrations; avoid to routing conductors near power signal cables .

CONFIGURATION AND CALIBRATION

1) Power-on the DAT1070 by a direct voltage between 10 ÷ 32 V or (only to configure) by a 9 V battery .

2) Remove the protection plastic cap on DAT1070.

3) Connect the interface PRODAT to the Personal Computer and to device. (see section “ DAT1070: PROGRAMMING” ).

4) Run the software PROSOFT.

5) Set the parameters of configuration .

6) Program the device.

CALIBRATION CONTROL With software PROSOFT running:

1) Connect on the input a calibrator setted with minimum and maximum values referred to the electric signal or to the temperature sensor to measure.

2) Set the calibrator at the minimum value.

3) Verify that the DAT1070 provides on output the minimum setted value.

4) Set the calibrator at the maximum value.

5) Verify that the DAT1070 provides on output the maximum setted value.

6) In case of regulation of value obtained in the step 3 and 5, use the ZERO and SPAN regulators of software PROSOFT. The variation introduced from these regulators must be calculated as percentage of the input range .

7) Program the device with the new parameters .

PROGRAMMING

Programming head mount

CONNECTIONS

Input

DAT1070 INPUT CONNECTIONS

Output

DAT1010 output connections

LOAD CHARACTERISTIC

DAT1040 LOAD CHARACTERISTIC

DIMENSIONS

DAT1070 DIMENSIONS

 

ISOLATION STRUCTURE

None